ST-7601S UL Cable Vertical-Tray Flaming Test Room(UL1685)

Introduction

ST-7601S UL Cable Vertical-Tray Flaming Test Room(UL1685)

Product Details

 

ST-7601S UL Cable Vertical-Tray Flaming Test RoomUL1685
Standards: According to the clause 9.6 & 9.7 of UL1685-2007, UL2556-2007
Scope: Apply to check the vertical-tray fire test for determining values of cable flame propagation and smoke release when the cables are subjected to a flaming ignition source. (It is nothing to the purpose of cables, such as the electric power, telecommunications etc.)
Main components: Main consist of Ignition source & supply fire control system, collection hood & exhaust duct flux control system, pressure measurement instrumentation of gas, smoke measurement instruments & temperature measurement system, flame height measurement system etc.
Main parameter:
1.   Test room: Fire resistance bricks for walls and which density is 1698kg/m3, Interface spray black paint, and the outer size of the room is W2438×D2438×H3353mm
2.   Door: Stainless steel frame and wired-glass door, the overall size is W0.9× H2.0m;
3.   Smoke collection hood: Which made by stainless steel, each side is to be sloped 400, the hood as a cube and each side length is 914mm, there is a dust mesh under the hood and each side length is 610mm;
4.   Observation window: Which as a square and each side length is 457mm, 1295mm distance from the lower side of the window to floor, 1143mm distance from right of the window to the wall;
5.   Air inlets: which size are 559×343mm, 914×305mm, 2438×343mm;
6.   Exhaust duct: L9000×φ406mm, install it at the centered in on the right side of the cube hood
7.   Cable tray: H2400mm, the rundle as a square which size is L305×W25×D25, and both rundles distance is 299mm;
8.   Burner: L341mm×D30mm with 242 holes;
9.   Gas flux: 13.2L/min, 0.1Mpa for gas pressure
10.Flux checking: The differential pressure flowmeter sense smoke pipeline flow speed , provide basis for the control of fan speed ;
11.Light transmittance: photocell sense the smoke density during the flaming;
12.Height of flame: Infrared visible light show the current height of the flame real-time;
13.Special software: Draw up the curve by the pip flow, smoke density, height of the flame ,and form a table automatically, through the printer printing;
14. Control system: 5.7inch color touch screen, PLC from Japanese Panasonic, SCM, 16 bits high-performance AD transform etc